DR RA7750.02 Standard System Monitored PSU

Disabled Refuge RA7750.02 Monitored PSU

STANDARD DISABLED REFUGE EVC SYSTEM MONITORED PSU

  • Provides powers for standard Disabled Refuge EVC system with up to 20-off outstations.
  • Standby power
  • Houses battery set for standby power
  • Lockable, surface/wall mount, enclosure
  • Mains fail monitoring (reported by master station)
  • Local mains fail alarm, with silence button
  • Status LEDs

ADDITIONAL INFORMATION

DESCRIPTION

The standard system monitored PSU is the Folknoll standard Disabled Refuge EVC system power supply and standby battery unit. The unit is usually mounted on a wall in an equipment room near to one of the standard system controllers. The PSU unit is supplied fully enclosed and ready for wall mounting. The unit is convection cooled and should be mounted in a cool place with room for convection cooling to take place. A single standard system monitored PSU will provide power for a complete Folknoll standard Disabled Refuge EVC system of up to 20-off outstations. When fitted with a standard system battery set the PSU will provide power for 24 hours standby and 30 minutes operation in the event of a main supply failure. The unit enables the mains supply to be monitored by the Disabled Refuge EVC system. Mains failure is reported by the master station. The PSU unit has local mains fail alarm which can be silenced by means of a SILENCE button located on the outside of the enclosure.

PART NUMBERS

RA7750.02 Surface mount, standard system PSU
RA7750.04 Standard system PSU battery set

SPECIFICATIONS

Enclosure: Mild steel (18 SWG)
Finish: Metallic Silver (Radon MW334E) painted
Mounting: Surface (5 holes in rear), 20m knockouts in top
Dimensions (surface mount): Width 400mm, Height 300mm, Depth 80mm (approx.)
ROHS: Compliant lead free construction
Power: 90V-264V ac,  <2amps,  47-63Hz.
Output: 19V d.c. min (battery) 30V d.c. max (mains)
Fuse (Input): T3.1A 250 V a.c.
Fuse (Load): 5A self setting Polyfuse
Fuse (Battery Bypass): 6.3A (not replaceable)